Service Equipment Other Service Equipment

CPT-II Fully Automatic Model Multi-functional CT PT Analyzer

Automatic Model CT PT Tester -- Model: CPT-II Application: Tests for current transformer: Excitation curve and parameters test Turns ratio test Ratio and phase error test Polarity mark check Coil resistance measurement Secondary loop burden measurement Error line curve test for protection CT Transient CT parameters test CT nameplate guess Tests for voltage transformer: Excitation curve test Turns ratio test Polarity test Secondary burden test Coil resistance test Applications

Max. Test Voltage 180V
Place of Origin China
Warranty One year
Knee Point Voltage 40kV
Size 485mm×356mm×183mm
Packaging Details CT PT Analyzer packed in veneer case
Product Description

Automatic Model CT PT Tester  --  Model: CPT-II

Application:

Tests for current transformer:

  1. Excitation curve and parameters test
  2. Turns ratio test
  3. Ratio and phase error test
  4. Polarity mark check
  5. Coil resistance measurement
  6. Secondary loop burden measurement
  7. Error line curve test for protection CT
  8. Transient CT parameters test
  9. CT nameplate guess

Tests for voltage transformer:

  1. Excitation curve test
  2. Turns ratio test
  3. Polarity test
  4. Secondary burden test
  5. Coil resistance test

 

Applications for CTPT analyzer:

  • CT nameplate check
  • CT parameters check in work burden
  • CT transient parameters analysis
  • CT ratio and phase error calibration
  • PT routine test

 

 

Parameters:

1

Test standards

IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13

2

Power supply

AC220V±10%,50Hz/60Hz±10%

3

Power output

0.1~125V (AC)

4

Current output

0.001~5A(RMS)

5

Power output

300VA

6

Max. knee voltage measurement

45kv

7

Current measurement range

0~10A (automatically change range in 0.1/0.4/2/10A)

8

Current measurement error

<±0.1%+0.01%FS

9

Voltage measurement range

0~200 V (automatically change range in 1V/10V/70V/200V)

10

Voltage measurement error

< ±0.1%+0.01%FS

11

Turns ratio measurement range

1~30000;

1~2000 error<0.05%; 2000~5000 error>0.1%; 5000~35000 error<0.2%

12

Phase measurement

error:±2min,resolution:0.01min

13

Coil resistance measurement

Range: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm)

Error< 0.2%RDG+0.02%FS Maximum resolution: 0.1mΩ

14

Temperature measurement

-50~100 Celsius degree, error<3 Celsius degree

15

CT Secondary burden

Range 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm)

Error <0.2%RDG+0.02%FS Maximum resolution 0.001ohm

16

PT Secondary burden

Range 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm)

Error <0.2%RDG+0.02%FS Maximum resolution: 0.1ohm

17

PT ratio measurement

Range: 1~30000, 1~5000 error<0.2%, 5000~30000 error<0.5%

18

Saved data groups

>1000groups

19

Work condition

Temperature:-10℃-50℃, moist:≤90%

20

Size

485mm×356mm×183mm

21

Weight

<15Kg

 

 

 

Real Picture:

 
Interested in this product?
Contact us now for more details and a custom quote.