Closed Loop Hall Effect Current Sensor 5A to 30A Pulsed DC AC Measurement 3.3V
High precision closed loop Hall effect current sensor for DC, AC, and pulsed currents. Rated input 5A to 30A with 0.625V output. Features galvanic isolation, fast response <500ns, and low linearity error ≤0.1%FS. UL94-V0 certified. Custom options available.
Metering Closed Loop Hall Effect Current Sensor Pulsed Current Measurement
TBC-PS3.3 series current sensor is two closed loop device based on the measuring principle of the hall effect,
with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of DC,AC or pulsed currents.
| Electrical data(Ta=25℃±5℃) |
|
Type Parameter |
TBC5PS3.3 | TBC10PS3.3 | TBC15PS3.3 | TBC25PS3.3 | TBC30PS3.3 | Unit |
|
Rated input (Ipn) |
5 | 10 | 15 | 25 | 30 | A |
| Measuring crange(Ip) | 12 | 24 | 36 | 50 | 60 | A |
| Turns ratio(Np/Ns) | 5:1000 | 3:960 | 2:960 | 1:1000 | 1:960 | T |
| Inside resistance | 25±0.1% | 20±0.1% | 20±0.1% | 25±0.1% | 20±0.1% | Ω |
| Rated output | 0.625±0.5% | 0.625±0.5% | 0.625±0.5% | 0.625±0.5% | 0.625±0.5% | V |
| Size of input pins | ø 0.6 | ø 0.8 | ø 1.0 | ø 1.4 | ø 1.6 | mm |
| Supply voltage |
+3.3±5% |
V | ||||
| Power consumption | ≤20+IpX(Np/Ns) | mA | ||||
Zero voltage |
@ Is=0 1.65±0.5% |
V | ||||
| Offset drift |
@ -40~+85℃ ≤±0.5 |
mV/℃ | ||||
| Linearity |
@ Ip=0-±Ipn ≤0.1 |
%FS | ||||
| Total precision |
≤±0.7 |
% | ||||
di/dt accurately followed |
>50 |
nS | ||||
| Response time | @ Ip=Ipn, 50 A/µS , 90% <500 | nS | ||||
| Bandwidth | @ -1db DC~100 | KHZ | ||||
| Galvanic isolation | @ 50HZ, AC, 1min 2.5 | KV | ||||
|
Applications |
Variable speed drives
Welding machine
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Electrochemical
DC motor drives
| Mechanical dimension(for reference only) |
Remarks:
1. All dimensions are in mm.
2. General tolerance ±1mm.
| Directions for use |
When the current will be measured goes through a sensor, the voltage will be measured at the output end.
(Note: The false wiring may result in the damage of the sensor).
Custom design in the different rated input current and the output voltage available.
|
Standards |
- UL94-V0
- EN60947-1:2004
- IEC60950-1:2001
- EN50178:1998
- SJ 20790-2000
| General date |
| Value | Unit | Symbol | |
| Operating temperature | -40 to +85 | ºC | TA |
| Storage temperature | -40 to +125 | ºC | TS |
| Mass(approx) | 12 | g | M |
| Characteristics chart |
Pulse current signal response characteristic Effects of impulse noise