Closed Loop Hall Effect Current Sensor 25A 50A for UPS DC AC Pulsed Current

TBC-DHT series closed loop hall effect sensor measures DC, AC or pulsed currents with galvanic isolation. Rated 25A or 50A, ±0.1% linearity, <1µs response time, 100kHz bandwidth. UL94-V0, EN60947 certified. Custom options available.

product name Hall Effect Current Sensor
Place of Origin CHINA
Packaging Details Little Carton Size:34*23*21CM;240pcs/Carton ;Large Carton Size:48*37*26CM;480pcs/Carton
Standard high precision
Model Number TBC-DHT
Mounting Type PCB Mounting
Product Description

Pulsed Current Low Current Hall Effect Sensor For Uninterruptible Power Supplies

 

TBC-DHT series current sensor is a closed loop device based on the measuring principle of the hall effect and null balance method, with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of DC, AC or pulsed currents.

 

Electrical data(Ta=25℃±5℃)

 

Type

Parameter
TBC25DHT TBC50DHT

 

Unit


Rated input (Ipn)
25 50 A

Measure current range(Ip)
60 120 A

Secondary Turns(Ns)
1000±1 2000±2 T

Secondary resister
40 80 Ω

Rated output (Isn)
@ Ip=±Ipn ±25±0.5% mA

Supply voltage
±15±5% V
Power consumption ≤20+Ip/Ns mA

Zero Offset current
@ Is=0 ±0.2 mA

Offset current drift
@ -40~+85℃ ≤±0.6 mA
Linearity @ Ip=0-±Ipn ≤0.1 %FS

Total precision
≤±0.7 %FS

di/dt accurately followed
>50 A/µS

Response time
@ Ip=Ipn,50 A/µS,10%-90% <1 µS

Bandwidth
@ -1db DC~100 KHZ

Galvanic isolation
@ 50HZ,AC,1min 2.5 KV

 

Applications

 

AC variable speed drives

Static converters for DC motor drives

Battery supplied applications

Uninterruptible Power Supplies (UPS)

Switched Mode Power Supplies(SMPS)

Power supplies for welding applications

 

Mechanical dimension(for reference only)

Remarks:

1. All dimensions are in mm.

2. General tolerance ±1mm

 

Directions for use

When the current will be measured goes through a sensor, the voltage will be measured at the output end.

(Note: The false wiring may result in the damage of the sensor)

Custom design in the different rated input current and the output voltage are available.

 

 

Standards

 

  • UL94-V0.
  • EN60947-1:2004
  • IEC60950-1:2001
  • EN50178:1998
  • SJ 20790-2000

 

General date

 

  Value Unit Symbol
Operating temperature -40 to +85 ºC TA
Storage temperature -40 to +125 ºC TS
Mass(approx) 9 g M

 

Characteristics chart

 

Pulse current signal response characteristic Effects of impulse noise

Interested in this product?
Contact us now for more details and a custom quote.