Portable Voltage Transformer Field Tester

The voltage transformer error tester has the function of measuring the voltage transformer error by the recursive method and measuring the voltage transformer error by the potential difference method, which is convenient for the on-site verification of the metering device. The on-site verification of voltage or transformer does not require standard transformer, booster, load box, voltage control box, and can be achieved by using very simple test wiring and operation, which

Price 4000-12000
Minimum Order Quantity 1
accuracy 0.05%
primary voltage 10KV,35KV,110KV,220KV
secondary voltage 100V,100/√3V
Product Description

The voltage transformer error tester has the function of measuring the voltage transformer error by the recursive method and measuring the voltage transformer error by the potential difference method, which is convenient for the on-site verification of the metering device.

The on-site verification of voltage or transformer does not require standard transformer, booster, load box, voltage control box, and can be achieved by using very simple test wiring and operation, which greatly reduces the work intensity and improves the work efficiency, and is convenient for on-site verification of transformer.

1: Error measurement part of low calibration high voltage transformer

Accuracy of the whole machine: 1/3 of the error limit of the tested voltage transformer

Test scope:

6kV/100V 10kV/100V 20kV/100V 35kV/100V

6kV/3/100V/3     10kV/3/100V/3      20kV/3/100V/3

35kV/3/100V/3             66kV/3/100V/3    110kV/3/100V/3

220kV/3/100V/3

Operating range of the tested voltage transformer: 80% to 120%

Secondary load: 0.0VA~300VA, COS φ=0.1~1.0

Accuracy range of the tested voltage transformer: 1.0, 0.5, 0.2, 0.1

Resistance and admittance measurement error 5.0%

   Measuring range: R: 0.00Ω~5.0Ω

   Y:  0.000mS~200.0mS

2: Voltage Transformer Calibration Instrument Part

Basic error:

In-phase component: DX=(2 words X x 2%+Y x 2%)±±

DY=(X x 2%+Y x 2% 5 words)±±

X "," Y "- instrument display values

Five Words "- Quantification Error of Instruments

Dial indicator: Level 1.

Measurement range: f: 0.0000% to 200.0%

    δ: 0.000~999.9

Rated working voltage: 100/3V, 100/V, 100V

Operating range of the tested voltage transformer: 20% to 200%

3: Instrument power consumption: 20VA

4: Instrument accuracy level: 0.05 level

5: Maximum external dimensions (cm): L46W35H13.5´´

6: Weight (kg): 11.0