MTL5549Y MTL Isolator Barriers Isolating Driver
MTL5549Y MTL Isolator Barriers Isolating Driver Eaton Crouse-Hinds series MTL5500 isolating driver featuring 2-channel analogue output, designed for valve positioners with line fault detection. This industrial-grade device operates on 20-35 Vdc power supply with HART communication support and comprehensive safety certifications. Product Specifications Product Name Eaton Crouse-Hinds series MTL5500 isolating driver Catalog Number MTL5549Y - FSM ASSESSED EAN 3066227675810
Condition
original brand new
Place of Origin
England
Warranty
one year
Packaging Details
original package
Shipping way
DHL FedEx express
Model Number
MTL5549Y
Product Description
MTL5549Y MTL Isolator Barriers Isolating Driver
Eaton Crouse-Hinds series MTL5500 isolating driver featuring 2-channel analogue output, designed for valve positioners with line fault detection. This industrial-grade device operates on 20-35 Vdc power supply with HART communication support and comprehensive safety certifications.
Product Specifications
| Product Name | Eaton Crouse-Hinds series MTL5500 isolating driver |
| Catalog Number | MTL5549Y - FSM ASSESSED |
| EAN | 3066227675810 |
| Dimensions | 109.8mm (L) × 118.8mm (H) × 15.8mm (W) |
| Weight | 150g |
| Product Type | Isolating driver |
Technical Characteristics
| Application | For 4-20mA HART valve positioners with line fault detection |
| Area Classification | Hazardous/Classified Locations |
| Standards | IEC, IECEx/ATEX |
| Hazardous Rating | Zone 0 |
| Operating Temperature | -20°C to 60°C |
| Storage Temperature | -40°C to 80°C |
| Humidity | 5-95% relative humidity |
Electrical Specifications
| Signal Type | Analogue output |
| Signal Range | 4-20mA |
| Response Time | Settles within 200µA of final value within 100ms |
| Number of Channels | 2 |
| Power Supply | 20-35 Vdc |
| Current Consumption | 70mA |
| Power Dissipation | 1.6W |
| Minimum Load Resistance | 90Ω (short circuit detection at <50Ω) |
| Maximum Load Resistance | 800Ω (16V at 20mA) |
| Input/Output Characteristics | Normal <6.0V, Open circuit <0.5mA |
Performance Features
- Communication Supported: HART protocol
- Switching Frequency: 500 Hz to 10 kHz
- Transfer Accuracy: Better than 20µA
- Temperature Drift: <1.0µA/°C
- Ripple: <40µA peak-to-peak
- Under/Over Range: Over range = 24mA (load ≤520Ω), Under range = 1mA
- Safety Integrity Level: SIL2 and SIL3 according to IEC61508
- Galvanic Isolation: 250V rms between safe-area circuits and power supply
- LED Indication: Green power indicator
- Mounting Method: T-section 35mm DIN rail
- Terminal Capacity: Accepts conductors up to 2.5mm² stranded or single-core
- Electrical Connection: Crimp ferrules
- EMC Compliance: EN61326