China MTL5561 DIN Rail Isolating IS Interface Unit Two, fully floating, loop powered for sale
China MTL5561 DIN Rail Isolating IS Interface Unit Two, fully floating, loop powered for sale
China MTL5561 DIN Rail Isolating IS Interface Unit Two, fully floating, loop powered for sale
China MTL5561 DIN Rail Isolating IS Interface Unit Two, fully floating, loop powered for sale
China MTL5561 DIN Rail Isolating IS Interface Unit Two, fully floating, loop powered for sale

MTL5561 DIN Rail Isolating IS Interface Unit Two, fully floating, loop powered

MTL5561 DIN Rail Isolating IS Interface Unit The MTL5561 is a loop-powered 2–channel interface for use with conventional fire and smoke detectors located in hazardous areas. Product type : Fire And Smoke Detector InterfaceNumber of channels : Two, fully floating, loop poweredLocation of fire and smoke detectors : Zone 0, IIC, T4–6 hazardous area if suitably certified Div. 1, Group A, hazardous areaInput voltage : 6 to 30V dcCurrent range : 1 to 40mA, nominalQuiescent safe

Input voltage 6 to 30V dc
Place of Origin UK/China
Packaging Details carton
Model Number MTL5561
Supply Ability 1000pcs per week
Certification HART
Product Description

MTL5561 DIN Rail Isolating IS Interface Unit

   The MTL5561 is a loop-powered 2–channel interface for use with conventional fire and smoke detectors located in hazardous areas.

     

  • Product type : Fire And Smoke Detector Interface

  • Number of channels : Two, fully floating, loop powered

  • Location of fire and smoke detectors : Zone 0, IIC, T4–6 hazardous area if suitably certified Div. 1, Group A, hazardous area

  • Input voltage : 6 to 30V dc

  • Current range : 1 to 40mA, nominal

  • Quiescent safe–area current at 20°C : (hazardous–area terminals open circuit) < 400µA at Vin = 24V per channel

  • Integral input polarity protection : Input circuit protected against reverse polarity

  • Minimum output voltage Vout at 20°C : For Vin = 25V: Vout = Vin – (0.38 x current in mA) – 2V, For Vin > 25V: Vout = 22.5V – (0.35 x current in mA)

  • Maximum output voltage : 28V from 300?

  • Transfer accuracy at 20°C : Better than 400µA

  • Temperature drift : < 4µA/°C ( 0°C to 60°C), < 15µA/°C (–20°C to 0°C)

  • Response time to step input Settles to within 5% of final value within 1.5ms

  • Power dissipation within unit : 0.7W maximum at 24V with 40mA signal (each channel) 0.9W maximum at 30V with 40mA signal (each channel)

  • Safety description for each channel Uo=28V Io=93mA Po=0.65W Um = 253V rms or dc

  • Shipping weight : 2 Kg


    Recommended Products

    Price: Negotiate
    Price: Negotiate
    Price: Negotiate
    Price: Negotiate
    Price: Negotiate
    Price: Negotiate
    Interested in this product?