PLC Systems Multifunctional Modules Integrated Communication Ethercat Remote I/O IP40
Decowell RS Series Integrated I/O EC2-S2 Communication Module For PLC Systems Product Description Decowell RS series integrated I/O EC2-S2 Communication Module RS series integrated l/O modules support a variety of industrial fieldbusprotocols, such as EtherCAT, PROFINET, EtherNet/lP, DeviceNet, etc. The I/O modules support a maximum of 32 channels of digital inputs/digi-tal outputs, and users can choose different I/O module componentsaccording to the actual needs, with single
Origin
Nanjing
Customization
Available | Customized Request
Packaging Details
Carton packing,LxW90x100x45.4mm.
HS Code
8538900000
Shipping Cost
about shipping cost and estimated delivery time.
Trademark
DECOWELL
Product Description
Decowell RS Series Integrated I/O EC2-S2 Communication Module For PLC Systems
RS series integrated l/O modules support a variety of industrial fieldbusprotocols, such as EtherCAT, PROFINET, EtherNet/lP, DeviceNet, etc. The I/O modules support a maximum of 32 channels of digital inputs/digi-tal outputs, and users can choose different I/O module componentsaccording to the actual needs, with single-slot and dual-slot chassisavailable.The RS series bus protocols are respectively
Each bus protocol of RS series supports 16DI NPN, 16DI PNP, 16DO NPN, 16DO PNP, 8DI8DO NPN, 8DI8DO PNP, 8DO relay respectively.
![Decowell RS Series Integrated I/O Ec2-S2 Communication Module, for PLC]()
Decowell RS series integrated I/O EC2-S2 Communication Module
RS series integrated l/O modules support a variety of industrial fieldbusprotocols, such as EtherCAT, PROFINET, EtherNet/lP, DeviceNet, etc. The I/O modules support a maximum of 32 channels of digital inputs/digi-tal outputs, and users can choose different I/O module componentsaccording to the actual needs, with single-slot and dual-slot chassisavailable.The RS series bus protocols are respectively
Each bus protocol of RS series supports 16DI NPN, 16DI PNP, 16DO NPN, 16DO PNP, 8DI8DO NPN, 8DI8DO PNP, 8DO relay respectively.
| Bus protocol | EtherCAT |
| Communication distance | 100m(distance from station to station) |
| Bus communication rate | 100Mbps |
| Communication cycle | Depends on EtherCAT master specifications |
| Refresh mode | Free running, DC synchronous running refresh |
| topology | Depends on the EtherCAT master specification |
| Node address | Configurable 0-192 (PLC only valid for Omron) |
| Input/output bytes | 128 |
| Enter/out the mailbox size | 256 |
| System power input | DC24V(18-30V) |
| IO power input | DC24V(18-30V) |
| The IO power supply provides current | 10A |
| Overcurrent protection | YES |
| Anti-reverse connection protection | YES |
| System side electrical isolation | YES |
| Operating ambient temperature | -10°C-55°C |
| Working ambient humidity | 10%-95% no condensation |
| Height of working environment | <2000m |
| Use ambient air | non-corrosive |
| EMC level | Zone A |
| Class of protection | IP40 |