SZ-03A-K8 Three Phase Reference Standard Meter 0.02% Accuracy 5-480V 10mA-120A Range
High-precision three-phase reference standard meter with 0.02% accuracy for voltage (5-480V) and current (10mA-120A) measurements. Features harmonic analysis, waveform display, RS232/RS485 interfaces, and CE certification. Ideal for calibration laboratories and electrical testing applications requiring exceptional accuracy and stability.
Origin
China
Measured Signal
Pulse Peak
Installation
Direct Connected
Usage
Multi-Functional Energy Meter, Watt-Hour Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Prepayment Meter, Reactive Energy Meter, Multi-rate Watt-hour Meters, Maximum Demand Meter
Place of Origin
CHINA
Theory
Electronic Meter
Product Description
SZ-03A-K8 Three Phase Reference Standard Meter
Application Conditions
| Parameter | Specification |
|---|---|
| Operating Temperature | -10°C to +40°C |
| Humidity | 45% to 75% |
| Altitude | <2500m |
| Voltage Supply | 220V±10%, 50/60Hz±2Hz |
| IP Class | IP30 |
| Certification | CE Conform |
Technical Specifications
| Parameter | Range | Accuracy | Display Range |
|---|---|---|---|
| Test Voltage | 5V-480V | ±0.02% | 5.000000V-480.000V |
| Test Current | 10mA-120A | ±0.02% (50mA-120A) ±0.05% (10mA-50mA) |
1.000000A-120.0000A |
| Phase Angle | 0°-360° | ±0.05° | 0.000001°-359.9999° |
| Frequency | 45Hz-65Hz | - | 45.000-65.000 |
| Dimensions | 432×131×470 mm (W×H×D) | ||
| Weight | 16 kg | ||
Power Measurement Accuracy
| Parameter | Accuracy |
|---|---|
| Active Power | ±0.02% (50mA-120A) |
| Reactive Power | ±0.05% (50mA-120A) |
| Apparent Power | ±0.05% (50mA-120A) |
Pulse Specifications
| Parameter | Specification |
|---|---|
| High Frequency Output | 1×10⁹ (0A-1A) 1×10⁸ (1A-10A) 1×10⁷ (10A-120A) |
| Low Frequency Output | 2×10-5×CH |
| Pulse Ratio | 1:01 |
| Output Level | 5V |
| Input Level | 24V |
| Input Frequency | 500Hz (Max) |
Advanced Features
- High precision 0.02% accuracy with long-term stability
- Synchronous measurement of multiple electrical parameters
- Accurate phase angle measurement with direct reactive power calculation
- Vector diagram visualization for comprehensive electrical analysis
- Voltage and current waveform display for detailed monitoring
- Harmonic analysis and display capabilities
- RS232 and RS485 interfaces for computer integration
- Simple calibration using only three energy constants
- Error calculation with low-frequency pulse input
Technology Overview
The SZ-03A-K8 series utilizes advanced technologies including high-speed DSP, CPLD, MCU, and ADC with self-calibration capabilities. This enables high-speed AC signal sampling and specialized digital arithmetic processing, resulting in a simplified structure while maintaining exceptional 0.02% relative error accuracy.