MTL4514D MTL5514D Switch Proximity Detector Interface with 10ms Response Time and 2A Contact Rating for Hazardous Areas
Industrial switch/proximity detector interface modules for hazardous environments. Features 10ms maximum response time, line fault detection, and dual relay control. MTL5514D supports up to 250V AC and 2A contact rating. Ideal for process control and safety systems requiring reliable sensor interface in harsh conditions.
Place of Origin
England
Packaging Details
standard carton packing
Hazardous–area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
Safe-area output
two, single pole relays with normally-open contact
Model Number
MTL4514
Supply Ability
100pcs per month
Product Description
The MTL4514D and MTL5514D switch/proximity detector interfaces enable control of two safe-area loads through relays using proximity detectors or switches located in hazardous areas. These industrial-grade modules feature line fault detection (LFD) that identifies open or short circuit conditions in field wiring, with status indication provided on the module housing.
Key Features & Capabilities
- Controls two safe-area loads via relays from hazardous area sensors
- Integrated line fault detection (LFD) for wiring integrity monitoring
- Visual fault indication on module top surface
- Configurable phase reversal selection
- LFD enable/disable switching capability
- Maximum response time of 10ms for rapid operation
- Designed for harsh industrial environments
Technical Specifications
| Parameter | MTL4514D | MTL5514D |
|---|---|---|
| Response Time | 10ms maximum | 10ms maximum |
| Safe Area Contact Rating | 10W, 0.5A, 35V dc | 250V ac, 2A, cosØ >0.7 40V dc, 2A, resistive load |
| Zone 2 Contact Rating | 10W, 0.5A, 35V dc | 35V, 2A, 100VA |
Product Visualization
Recommended Products
Price: negotiable
Price: negotiable
Price: negotiable
Interested in this product?
Contact us now for more details and a custom quote.