Intelligent fire safety guard 24 hours fire monitor for large space using Product Overview INTELLIGENT FIRE MONITOR AUTOMATIC FIRE SPRINKLER SYSTEM Our intelligent fire monitor adopts infrared thermal imaging principle and air-to-air missile tracking technology,It has the functions of real-time measurement and calculation of the real-time temperature of the fire, automatic tracking of the fire, automatic spraying to extinguish, and automatic water shutoff after the fire is
Intelligent fire safety guard 24 hours fire monitor for large space using




|
No
|
Item
|
Standard &Requirements
|
Inspection results
|
|
|
|
1
|
Rated working pressure (MPa)
|
≤0.8
|
0.6
|
/
|
|
|
2
|
Rated flow (L / s)
|
20×(1±8%)
|
20.1
|
/
|
|
|
3
|
Maximum protection radius(m)
|
≥50
|
50
|
/
|
|
|
4
|
Jet radius (m)
|
≥55
|
55
|
/
|
|
|
5
|
Monitoring radius(m)
|
≥80
|
80
|
/
|
|
|
6
|
Positioning time(s)
|
≤60
|
59
|
60
|
|
|
7
|
Installation height (m)
|
8~15
|
8
|
15
|
|
|
8
|
Horizontal swing angle(°)
|
≥180
|
360
|
|
|
|
9
|
Minimum pitch profile(°)
|
-90~+30
|
-90~+30
|
|
|
|
10
|
working temperature
|
4~55℃ ≤95%RH
|
4~55℃ ≤95%RH
|
|
|
|
11
|
Guidance system
|
Φ 15.5 ± 0.5
|
Φ 15.5 ± 0.5
|
|
|