XL5 Programmable Logic Controller DC 24V 16 I/O PLC Programming Device
Compact and practical slim PLC with 16 I/O points, transistor output, and DC24V power supply. Supports high-speed pulse output, AB phase counting, up to 16 expansion modules, and USB download. Offers 12x faster processing than XC series, with clock and data retention.
XL5 series PLC
Product description
Slim PLC, compact and practical, saving installation space
Support 2 ~ 4 channels of high-speed pulse output and 3 ~ 4 channels of AB phase high-speed counting
8 / 16 / 32 points input and 8 / 16 / 32 points output; Transistor output, DC24V power supply
Up to 16 expansion modules and 1 ED module can be expanded externally
Support USB port high-speed download
It has higher processing speed, about 12 times that of XC series
With clock and data power down holding function
Support basic logic control and data operation
Support X-NET fieldbus, PID, external interrupt, C function block, MODBUS communication and other functions
|
Model list
Note: PNP PLC can be customized.
Function configuration table × Not support √ support
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Note: all models are equipped with clock function as standard.
General Specifications
| Item | Specification |
| Insulation voltage | Above DC 500V 2MΩ |
| Anti noise | Noise voltage 1000Vp-p 1us pulse 1 minute |
| Air | No corrosive and combustible gas |
| Ambient temperature | 0℃~55℃ |
| Ambient humidity | 5%~95% (no condensation) |
| USB port | USB port, XNET protocol, for upload/download porgram and monitoring |
| COM1 | RS232, connect upper computer, HMI to programming and debug |
| COM2 | RS485, connect intelligent instruments, frequency converters, etc |
| COM3 | For left expansion ED module |
| Installation | It can be fixed with M3 screws or directly installed on the guide rail |
| Ground (FG) | The third kind of grounding (not common grounding with strong current system) |
Functional Specifications
| Item | Specification | |||||
| Program execution mode | Loop scan mode | |||||
| Programming mode | Command and ladder chart | |||||
| Processing speed | 0.05us | |||||
| Power-off retentive | FlashROM and 3V lithium battery | |||||
| User program capacity ※1 | 512kB | |||||
|
I/O points ※2 |
Total points | 16 points | 32 points | 64 points | ||
| Input points |
8 points X0~X7 |
16 points X0~X17 | 32 points X0~X37 | |||
| Output points |
8 points Y0~Y7 |
16 points Y0~Y17 | 32 points Y0~Y37 | |||
| Internal coils (X)※3 | 1280 points: X0~X77, X10000~X11777, X20000~X20177, X30000~X30077 | |||||
| Internal coils (Y) ※4 | 1280 points: Y0~Y77, Y10000~Y11777, Y20000~Y20177, Y30000~Y30077 | |||||
|
Internal coils (M, HM) |
87000 points | M0~M69999【HM0~HM11999】※5 | ||||
| Special use ※6 SM0~SM4999 | ||||||
| Flow (S) | 9000 points | S0~S7999【HS0~HS999】 | ||||
| Timer (T) | Points | 7000 points | T0~T4999【HT0~HT1999】 | |||
| Spec |
100ms timer: 0.1~3276.7s 10ms timer: 0.01~327.67s 1ms timer: 0.001~32.767s |
|||||
| Counter (C) | Points | 7000 points | C0~C4999【HC0~HC1999】 | |||
| Spec |
16-bit counter: K0~32,767 32-bit counter: -2147483648~+2147483647 |
|||||
| Data register (D) | 100000 words | D0~D69999【HD0~HD24999】※5 | ||||
| Special use ※6 SD0~SD4999 | ||||||
|
FlashROM register (FD) |
14192 words | FD0~FD8191 | ||||
| Special use ※6 SFD0~SFD5999 | ||||||
| High speed processing ability | High speed counter, pulse output, external interruption | |||||
| Password protection | 6-bit ASCII | |||||
| Self-diagnose function | Power on self-check, monitor timer, grammar check | |||||
Notes:
※ 1: User program capacity refers to the maximum program capacity during secret download.
※ 2: I / O points refer to the number of terminals that users can access and output signals from the outside.
※ 3: X refers to the internal input relay, and X exceeding I points can be used as intermediate relay.
※ 4: y refers to the internal output relay. Y exceeding O points can be used as an intermediate relay.
※ 5: [ ] flag, which is the default power-off holding area and cannot be changed.
※ 6: Special use refers to the special purpose register occupied by the system, which can not be used for other purposes.
※ 7: The numbers of input coils and output relays / transistors are octal numbers, and the numbers of other memories are decimal numbers.
※ 8: I / O without real connection with peripheral equipment can be used as fast internal relay.