China Phase Angle Error CT PT Test Set for sale
China Phase Angle Error CT PT Test Set for sale

Phase Angle Error CT PT Test Set

Digital Transformer Tester HEWE series CT PT Test Equipment Comparator Technical Parameter Accuracy class 2 Current range 5A, 1A Voltage range 100V,100/√3V Percentage Error Less than 1.5%*FS Basic Error When testing CT PT error & impedance & admittance, the error will not beyond: ΔX=±(X*2%+Y*2%+Dx) ΔY=±(X*2%+Y*2%+Dy) ΔX: basic error limit value of in-phase component ΔY: basic error limit value of Quadrature Component X: Indication absolute value of in-phase component Y:

Place of Origin China
Packaging Details Wooden Package
Test Function Ratio, Ratio error, phase angle error......
Model Number HEWE series
Accuracy class 2
Supply Ability 30 sets per month
Product Description

 

Digital Transformer Tester HEWE series CT PT Test Equipment Comparator

 

 

Technical Parameter

Accuracy class 2
Current range 5A, 1A
Voltage range 100V,100/√3V
Percentage Error Less than 1.5%*FS
Basic Error
When testing CT PT error & impedance & admittance, the error will not beyond:

ΔX=±(X*2%+Y*2%+Dx)

ΔY=±(X*2%+Y*2%+Dy)

ΔX: basic error limit value of in-phase component

ΔY: basic error limit value of Quadrature Component

X: Indication absolute value of in-phase component

Y: Indication absolute value of Quadrature Component

Dx & Dy: Zero error and Quantizing Error

When testing CT & PT, Dx,Dy=1(or 2)%*(Error limit value of CT & PT

When testing Z & Y, Dx,Dy= 3 digits

 

Measure Range & Resolution

CT PT class Test Range Resolution
In-phase component Quadrature Component In-phase component Quadrature Component
0.01 ±0.4000 ±13.752 0.0001% 0.001'
0.02
0.05
0.1 ±4.000 ±137.52 0.001% 0.01'
0.2
0.5
1.0 ±40.00 ±999.9 0.01% 0.1'
Impedance Measure Range & Resolution
Range Measure Range (Ω) Resolution
5A ±1.000 0.0001
1A ±6.000 0.0001
Admittance Measure Range & Resolution
Range Measure Range (mS) Resolution
100V ±9.9999 0.0001
57.7V ±9.9999 0.0001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Features

 

1) LCD display

2) Test of ratio, ratio error, phase angle error, impedance, admittance

3) Test data values are all displayed

4) Used for testing of class 1 to 0.01 instrument transformer with rated current 5A and 1A, 

    rated voltage 100V, 100V√3V

5) Display ratio error & phase angle error of all test points under rated burden or lower limit

    burden 1%-120% Rated current or 20%-120% rated voltage

 